| Model No | M30B | M45 | M90 | M125 | M175 | M350 |
|---|---|---|---|---|---|---|
| Max Motor Size (1) kW / HP | 37 / 55 | 55 / 75 | 110 / 150 | 150 / 200 | 200 / 270 | 370 / 500 |
| Max Starts/Hr (2) | 9 | 7 | 6 | 7 | 5 | 4 |
| Max Consecutive Starts (3) | 4 | 4 | 4 | 5 | 4 | 4 |
| Max Rotor Starting Current Amps | 140 | 275 | 425 | 525 | 625 | 1100 |
| Max Rotor Voltage (4) Volts | 600 | 600 | 800 | 800 | 1000 | 1200 |
| Max Rotor Voltage (HD) (5) Volts | 500 | 500 | 550 | 600 | 750 | 900 |
| Impedance (6) Ohms | 7.0 | 4.0 | 3.5 | 2.5 | 3.0 | 2.3 |
| Coil Insulation Rating | Class F (150°C), 4,000Vac winding-ground proof test | |||||
| Thermal Overload Cut-out (7) | 250Vac, 10A or 30Vdc, 5A max Normally closed | |||||
| Dimensions (8) mm See Mechanical Outline drawing | ||||||
| Height A | 250 | 260 | 255 | 360 | 360 | 430 |
| Width B | 305 | 325 | 365 | 365 | 365 | 500 |
| Depth C | 320 | 330 | 420 | 425 | 420 | 500 |
| Body Width D | 250 | 270 | 320 | 320 | 320 | 420 |
| Fixing Holes Side to Side E | 280 | 300 | 340 | 340 | 340 | 470 |
| Fixings Front to Back F | 233 | 257 | 320 | 320 | 320 | 360 |
| Rear Fixings G | 25 | 25 | 30 | 30 | 30 | 70 |
| Fixing Hole Size H | 10 | 10 | 10 | 10 | 10 | 12 |
| Fixing Studs Side to Side I | 215 | 247 | 285 | 285 | 285 | 370 |
| Channel Height J | 37 | 37 | 37 | 37 | 37 | 37 |
| Front Panel Inset K | - | - | - | - | - | 95 |
| Load Studs L | M8 | M8 | M10 | M10 | M12 | M12 |
| Overload Cut-out Studs L | M6 | M6 | M6 | M6 | M6 | M6 |
| Weight (9) kg | 27 | 36 | 54 | 75 | 81 | 165 |
| Operating Environment | -25°C to +50°C ambient, 0-95% RH (non-condensing) | |||||
Notes (x):
1.
With 50/60Hz, 3
phase supply. For other supply arrangements contact ADWEL.
It may be possible to parallel models for greater capacity in particular
circumstances. Please consult ADWEL with specific details.
2.
This is
based on the maximum motor size starting against 1.5 x full load torque for 15
secs, mounted in a typical unventilated metallic enclosure. For heavier duties
extra or forced ventilation may be required, or a larger Inducer chosen.
3.
Maximum
consecutive starts are from cold. Note that the motor rating may also limit
consecutive starts.
4.
Normal
starting duties, occasional inching in both directions.
5.
Heavy
inching, and plug braking.
6.
Impedance is
approximate per coil at 50Hz, full load, 100% tapping. Increase 12% for 60Hz. Typical PF is 0.8.
Tappings at 100%, 84% and 56% per coil allow a choice of star and delta
impedances from 100% down to 3% in 17 steps.
7.
The Thermal
Overload Cut-out should be wired to trip the starting system in case of overload
(contacts open).
8. On the M30, M45, M90, M125 and M175 the mounting channels can be removed and the Inducer mounted on the M8 studs protruding from the bottom of the rubber mounts. This allows these Inducers to be mounted in a 400mm deep enclosure.
9. Weight is without packing. For normal road shipment, the Inducers are mounted on 50 x 75 x 430mm wooden bearers (to allow fork-lift carriage) and shrink wrapped. For air/sea export, extra packing can be arranged.